TRACAL CV

WATER TREATMENT FOR STEAM BOILERS

PROPERTIES  :
Product of the latest generation in water treatment for steam boiler feed.
Its correct application stabilizes 100% of calcium, magnesium, silica and iron inside the boiler, allowing its elimination through the purge. It completely prevents scale, keeping the exchange surfaces clean.
It increases the performance of the facilities with the consequent energy savings by increasing the transfer capacity and making it possible to reduce the level of purges.

DOSAGE :
The exact doses should be adjusted for each particular installation, however, on average, quantities of the order of 50 ppm can be established. by degree of hardness of the contribution water (50grs / m3 of contribution water by degree of hardness).
The product must be added in all cases by proportional dosing system, adding the product in the condensate collection tank or the boiler feed.

SAFETY ADVISES :
H302 Harmful if swallowed. H314 Causes severe skin burns and serious eye damage. P270 Do not eat, drink or smoke during use. P280 Wear gloves / clothing / glasses / protective mask. P310 Immediately call a TOXICOLOGICAL INFORMATION CENTER or a doctor. P405 Store locked up. P501 Dispose of contents / container in … P301 + P330 + P331 IF SWALLOWED: Rinse mouth. DO NOT induce vomiting. P305 + P351 + P338 IF IN EYES: Rinse cautiously with water for several minutes. Remove contact lenses, if worn and easy. Continue rinsing. Contains: potassium hydroxide, caustic potash.

Type of packaging  :
Carafes of 30-60 Liters.

RECORDS  :
Nº article: 102125
Industrial Registry: 154069
Review / Date: 15 / March / 2016

PHYSICAL PROPERTIES :
Appearance : Transparent liquid
Color : Colorless
Density : 1.10
Pure pH : 13
Active matter : 14,1%

QUALITATIVE COMPOSITION :
Chelating agents
Dispersing agents
Corrosion inhibitors
Inorganic alkalis

 

WARNINGS:
The suggestions and recommendations on the use of our products meet our most knowledge at the time of writing this data sheet. We are not responsible for any possible negligence in handling. Compliance with all laws, including those in the protection of industrial property rests solely with the users of our products.